Special register device on PLC DELTA

 

Delta PLC programmer is a control system using electrical operation. It is easy to control storage, easy to expand, and the functions of sequence/position control, timer and check-out/output are widely used in industrial control.

For each PLC brand has its own special memory areas, Below are the PLC DELTA special register memory areas.

Special M bit on PLC DELTA

M1000*

Monitor normally open contact

M1001*

Monitor normally closed contact

M1002*

Enable single positive pulse at the moment when RUN is activate (Normally OFF)

M1003*

Enable single negative pulse at the moment when RUN is activate (Normally ON)

M1004*

ON when syntax errors occur

M1008*

Watchdog timer (ON: PLC WDT time out)

M1009

Indicate LV signal due to 24VDC insufficiency

M1011*

10ms clock pulse, 5ms ON/5ms OFF

M1012*

100ms clock pulse, 50ms ON / 50ms
OFF

M1013*

1s clock pulse, 0.5s ON / 0.5s OFF

M1014*

1 min clock pulse, 30s ON / 30s OFF

M1015*

Enable high-speed timer

M1016*

Indicate Year display mode of RTC.

M1017*

±30 seconds correction on real time clock

M1018

Flag for Radian/Degree, ON for degree

M1020

Zero flag

M1021

Borrow flag

M1022

Carry flag

M1024

COM1 monitor request

M1025*

Indicate incorrect request for
communication

M1026

RAMP mode selection

M1027

PR output mode selection (8/16 bytes)

M1028

Switch T64~T126 timer resolution   (10ms/100ms). ON =10ms

M1029*

CH0 (Y0, Y1) pulse output execution completed.

M1030*

Pulse output Y1 execution completed

M1031*

Clear all non-latched memory

M1032*

Clear all latched memory

M1033*

Output state latched at STOP

M1034*

Disable all Y outputs

M1035*

Enable X7 input point as RUN/STOP switch

M1037*

Enable 8-sets SPD function (Has to be used with D1037) (SE does not support this function.)

M1038

Switch T200~T255 timer resolution    (10ms/1ms). ON = 1ms

M1039*

Fix scan time

M1040

Disable step transition

M1041

Step transition start

M1042

Enable pulse operation

M1043

Zero return completed

M1044

Zero point condition

M1045

Disable “all output reset” function

M1046

Indicate STL status

M1047

Enable STL monitoring

M1048

Indicate alarm status

M1049

Enable alarm monitoring

M1050

Disable interruption I000 / I001

M1051

Disable interruption I100 / I101

M1052

Disable interruption I200 / I201

M1053

Disable interruption I300 / I301

M1054

Disable interruption I400 / I401

M1055

Disable interruption I500 / I501

M1056

Disable interruption I600~I699

M1057

Disable interruption I700~I799
Disable interruption I805~I899 (V2.00 and
above are supported.)

M1058

COM3 monitor request

M1059

Disable high-speed counter interruptions I010~I080

M1060

System error message 1

M1061

System error message 2

M1062

System error message 3

M1063

System error message 4

M1064

Incorrect use of operands

M1065

Syntax error

M1066

Loop error

M1067*

Program execution error

M1068*

Execution error locked (D1068)

M1070

Switching clock pulse of Y1 for PWM instruction (ON: 100us; OFF: 1ms)

M1071

Switching clock pulse of Y3 for PWM instruction (ON: 100us; OFF: 1ms)

M1072

PLC status (RUN/STOP), ON = RUN

M1075

Error occurring when write in Flash ROM

M1078

Y0/CH0(Y0, Y1) pulse output pause  (immediate)

M1079

Y1 pulse output pause (immediate)

M1080

COM2 monitor request

M1081

Changing conversion mode for FLT  instruction

M1083*

Selecting X6 pulse-width detecting mode.
M1083 = ON, detecting pulse-width when
X6 = ON; M1083 = OFF, detecting pulse
width when X6 = OFF.

M1084*

Enabling X6 Pulse width detecting function. (has to be used with M1183 and D1023)

M1085

Selecting DVP-PCC01 duplicating function

M1086

Enabling password function for DVP PCC01

M1088

Matrix comparison.
Comparing between equivalent values
(M1088 = ON) or different values (M1088
= OFF).

M1089

Indicating the end of matrix comparison.
When the comparison reaches the last bit,
M1089 = ON.

M1090

Indicating start of matrix comparison.
When the comparison starts from the first
bit, M1090 = ON.

M1091

Indicating matrix searching results. When
the comparison has matched results,
comparison will stop immediately and
M1091 = ON.

M1092

Indicating pointer error. When the pointer
Pr exceeds the comparison range, M1092
= ON

M1093

Matrix pointer increasing flag. Adding 1 to
the current value of the Pr.

M1094

Matrix pointer clear flag. Clear the current
value of the Pr to 0

M1095

Carry flag for matrix rotation / shift /
output.

M1096

Borrow flag for matrix rotation/shift/input

M1097

Direction flag for matrix
rotation/displacement

M1098

Counting the number of bits which are “1”
or “0”

M1099

ON when the bits counting result is “0”

M1102*

Y2/CH1 (Y2, Y3) pulse output execution
completed

M1103*

Y3 pulse output completed

M1104

Y2/CH1 (Y2, Y3) pulse output pause
(immediate)

M1105

Y3 pulse output pause (immediate)

M1106

Zero point selection. M1106=ON, change
the zero point to the right of DOG switch
for zero return on CH0.

M1107

Zero point selection. M1107=ON, change
the zero point to the right of DOG switch
for zero return on CH1.

M1108

Y0/CH0 (Y0, Y1) pulse output pause
(ramp down)

M1109

Y1 pulse output pause (ramp down)

M1110

Y2/CH1 (Y2, Y3) pulse output pause
(ramp down)

M1111

Y3 pulse output pause (ramp down)

M1112

Switching clock pulse of Y0 for PWM
instruction (ON: 100us; OFF: 1ms)

M1113

Switching clock pulse of Y2 for PWM
instruction (ON: 100us; OFF: 1ms)

M1119*

Enable 2-speed output function of
DDRVI/DDRVA instructions

M1120*

Retaining the communication setting of
COM2 (RS-485), modifying D1120 will be
invalid when M1120 is set.

M1121

For COM2(RS-485), data transmission
ready

M1122

For COM2(RS-485), sending request

M1123

For COM2(RS-485), data receiving
completed

M1124

For COM2(RS-485), data receiving ready

M1125

For COM2(RS-485), communication ready
status reset

M1126

For COM2(RS-485), set STX/ETX as user
defined or system defined

M1127

For COM2(RS-485), data sending /
receiving / converting completed. (RS
instruction is not supported)

M1128

For COM2(RS-485),
Transmitting/Receiving status Indication

M1129

For COM2(RS-485), receiving time out

M1130

For COM2(RS-485), STX/ETX selection

M1131

For COM2(RS-485), ON when
MODRD/RDST/MODRW data is being
converted from ASCII to Hex

M1132

ON when there are no communication
related instructions in the program

M1136*

For COM3(RS-485/USB), retaining
communication setting

M1137

Retain DNET mapping data during non
executing period

M1138*

For COM1 (RS-232), retaining
communication setting. Modifying D1036
will be invalid when M1138 is set.

M1139*

For COM1(RS-232), ASCII/RTU mode
selection (OFF: ASCII; ON: RTU)

M1140

For COM2 (RS-485), MODRD / MODWR
/ MODRW data receiving error

M1141

For COM2 (RS-485), MODRD / MODWR
/ MODRW parameter error

M1142

Data receiving error of VFD-A handy
instructions

M1143*

For COM2(RS-485), ASCII/RTU mode
selection (OFF: ASCII; ON: RTU)

M1148

After the instruction DELAY is executed,
the execution of the program following
DELAY is delayed for 5us.

M1156*

Enabling the mask and alignment mark
function on I400/I401(X4) corresponding
to Y0

M1158*

Enabling the mask and alignment mark
function on I600/I601(X6) corresponding
to Y2

M1161

8/16 bit mode (ON = 8 bit mode)

M1162

Switching between decimal integer and
binary floating point for SCLP instruction.
ON: binary floating point; OFF: decimal
integer

M1167

16-bit mode for HKY input

M1168

Designating work mode of SMOV

M1177

Enable the communication instruction for
Delta VFD series inverter.
ON: VFD-A (Default), OFF: other models
of VFD

M1178

Enable knob VR0

M1179

Enable knob VR1

M1180

The EX2/SX2 model reads analog-to
digital values immediately.

M1181

The EX2/SX2 model outputs digital-to
analog values immediately.

M1182*

M1182 = ON, disable auto-mapping
function when connected with left-side
modules.
n For SA2 /SX2/SE models, values of
AIO modules will be auto-mapped to
D9800 and above.
n If the left side is connected with a
communication module, additional 10
words will be occupied. Ex: 04AD-SL
+ EN01-SL + SA2, average value of
Ch1~Ch4 of 04AD-SL maps to
D9810~D9813.

M1183*

M1183 = ON, disable auto mapping
function when connected with special
modules
#: ES2/EX2: OFF; SS2/SA2/SX2/SE: ON
(maps to D9900 and above)

M1190

Set Y0 high speed output as 0.01 ~ 10Hz

M1191

Set Y1 high speed output as 0.01 ~ 10Hz

M1192

Set Y2 high speed output as 0.01 ~ 10Hz

M1193

Set Y3 high speed output as 0.01 ~ 10Hz

M1200

C200 counting mode (ON: count down)

M1201

C201 counting mode (ON: count down)

M1202

C202 counting mode ON: count down)

M1203

C203 counting mode (ON: count down)

M1204

C204 counting mode (ON: count down)

M1205

C205 counting mode (ON :count down)

M1206

C206 counting mode (ON: count down)

M1207

C207 counting mode (ON: count down)

M1208

C208 counting mode (ON: count down)

M1209

C209 counting mode (ON: count down)

M1210

C210 counting mode (ON: count down)

M1211

C211 counting mode (ON: count down)

M1212

C212 counting mode (ON: count down)

M1213

C213 counting mode (ON: count down)

M1214

C214 counting mode (ON: count down)

M1215

C215 counting mode (ON: count down)

M1216

C216 counting mode (ON: count down)

M1217

C217 counting mode (ON: count down)

M1218

C218 counting mode (ON: count down)

M1219

C219 counting mode (ON: count down)

M1220

C220 counting mode (ON: count down)

M1221

C221 counting mode (ON: count down)

M1222

C222 counting mode (ON: count down)

M1223

C223 counting mode (ON: count down)

M1224

C224 counting mode (ON: count down)

M1225

C225 counting mode (ON: count down)

M1226

C226 counting mode (ON: count down)

M1227

C227 counting mode (ON: count down)

M1228

C228 counting mode (ON: count down)

M1229

C229 counting mode (ON: count down)

M1230

C230 counting mode (ON: count down)

M1231

C231 counting mode (ON: count down)

M1232

C232 counting mode (ON: count down)

C232 counter monitor (ON: count down)

M1233

C233 counter monitor (ON: count down)

M1178

Enable knob VR0

M1179

Enable knob VR1

M1180

The EX2/SX2 model reads analog-to
digital values immediately.

M1181

The EX2/SX2 model outputs digital-to
analog values immediately.

M1182*

M1182 = ON, disable auto-mapping
function when connected with left-side
modules.
n For SA2 /SX2/SE models, values of
AIO modules will be auto-mapped to
D9800 and above.
n If the left side is connected with a
communication module, additional 10
words will be occupied. Ex: 04AD-SL
+ EN01-SL + SA2, average value of
Ch1~Ch4 of 04AD-SL maps to
D9810~D9813.

M1183*

M1183 = ON, disable auto mapping
function when connected with special
modules
#: ES2/EX2: OFF; SS2/SA2/SX2/SE: ON
(maps to D9900 and above)

M1190

Set Y0 high speed output as 0.01 ~ 10Hz

M1191

Set Y1 high speed output as 0.01 ~ 10Hz

M1192

Set Y2 high speed output as 0.01 ~ 10Hz

M1193

Set Y3 high speed output as 0.01 ~ 10Hz

M1200

C200 counting mode (ON: count down)

M1201

C201 counting mode (ON: count down)

M1202

C202 counting mode ON: count down)

M1203

C203 counting mode (ON: count down)

M1204

C204 counting mode (ON: count down)

M1205

C205 counting mode (ON :count down)

M1206

C206 counting mode (ON: count down)

M1207

C207 counting mode (ON: count down)

M1208

C208 counting mode (ON: count down)

M1209

C209 counting mode (ON: count down)

M1210

C210 counting mode (ON: count down)

M1211

C211 counting mode (ON: count down)

M1212

C212 counting mode (ON: count down)

M1213

C213 counting mode (ON: count down)

M1214

C214 counting mode (ON: count down)

M1215

C215 counting mode (ON: count down)

M1216

C216 counting mode (ON: count down)

M1217

C217 counting mode (ON: count down)

M1218

C218 counting mode (ON: count down)

M1219

C219 counting mode (ON: count down)

M1220

C220 counting mode (ON: count down)

M1221

C221 counting mode (ON: count down)

M1222

C222 counting mode (ON: count down)

M1223

C223 counting mode (ON: count down)

M1224

C224 counting mode (ON: count down)

M1225

C225 counting mode (ON: count down)

M1226

C226 counting mode (ON: count down)

M1227

C227 counting mode (ON: count down)

M1228

C228 counting mode (ON: count down)

M1229

C229 counting mode (ON: count down)

M1230

C230 counting mode (ON: count down)

M1231

C231 counting mode (ON: count down)

M1232

C232 counting mode (ON: count down)

C232 counter monitor (ON: count down)

M1233

C233 counter monitor (ON: count down)

M1312

For COM1(RS-232), sending request
(Only applicable for MODRW and RS
instruction)

M1313

For COM1(RS-232), ready for data
receiving (Only applicable for MODRW
and RS instruction)

M1314

For COM1(RS-232), data receiving
completed (Only applicable for MODRW
and RS instruction)

M1315

For COM1(RS-232), data receiving error
(Only applicable for MODRW and RS
instruction)

M1316

For COM3(RS-485), sending request
(Only applicable for MODRW and RS
instruction)

M1317

For COM3(RS-485), ready for data
receiving (Only applicable for MODRW
and RS instruction)

M1318

For COM3(RS-485), data receiving
completed (Only applicable for MODRW
and RS instruction)

M1319

For COM3(RS-485), data receiving error
(Only applicable for MODRW and RS
instruction)

M1320*

For COM3 (RS-485), ASCII/RTU mode
selection. (OFF: ASCII; ON: RTU)

M1334*

Close the conditional contact and to
enable the instructions PLSR, DPLSR Y0,
DDRVI, DDRVA CH0(Y0/Y1) to execute
ramp-down (ON: Enable; OFF: Disable)
(available for ES2 V3.42/ES2-C/ES2-E:
V3.48/SS2 V3.28/SA2 V2.86/26SE
V2.0/SX2 V2.86 or later versions)

M1335*

Close the conditional contact and to
enable the instructions PLSR/DPLSR
Y2/DDRVI/DDRVA CH1(Y2/Y3) (ON:
Enable; OFF: Disable) (available for ES2
V3.42/ES2-C/ES2-E: V3.48/SS2
V3.28/SA2 V2.86/26SE V2.0/SX2 V2.86
or later versions)

M1346*

Output clear signals when ZRN is
completed

M1347

Auto-reset Y0 when high speed pulse
output is completed

M1348

Auto-reset Y1 when high speed pulse
output is completed

M1349

When M1349 is ON, the CANopen
function is enabled. (Only for DVP-ES2-
C)

M1350*

Enable PLC LINK

M1351*

Enable auto mode on PLC LINK

M1352*

Enable manual mode on PLC LINK

M1353*

Enable access up to 50 words through
PLC LINK (If M1353 is ON,
D1480~D1511 are latched devices.)

M1354*

Enable simultaneous data read/write in a
polling of PLC LINK

M1355*

Select Slave linking mode in PLC LINK
(ON: manual; OFF: auto-detection)

M1356*

Enable station number selection function.
When both M1353 and M1356 are ON,
the user can specify the station number
in D1900~D1931

M1357*

Enabling the detection of X0’s input pulse
frequency (ON: Enable; OFF: Disable)

M1358*

Enabling the detection of X1’s input pulse
frequency (ON: Enable; OFF: Disable)

M1359*

Enabling the detection of X2’s input pulse
frequency (ON: Enable; OFF: Disable)

M1360*

Slave ID#1 status on PLC LINK network

M1361*

Slave ID#2 status on PLC LINK network

M1362*

Slave ID#3 status on PLC LINK network

M1363*

Slave ID#4 status on PLC LINK network

M1364*

Slave ID#5 status on PLC LINK network

M1365*

Slave ID#6 status on PLC LINK network

M1366*

Slave ID#7 status on PLC LINK network

M1367*

Slave ID#8 status on PLC LINK network

M1368*

Slave ID#9 status on PLC LINK network

M1369*

Slave ID#10 status on PLC LINK network

M1370*

Slave ID#11 status on PLC LINK network

M1371*

Slave ID#12 status on PLC LINK network

M1372*

Slave ID#13 status on PLC LINK network

M1373*

Slave ID#14 status on PLC LINK network

M1374*

Slave ID#15 status on PLC LINK network

M1375*

Slave ID#16 status on PLC LINK network

M1376*

Indicate Slave ID#1 data interchange
status on PLC LINK

M1377*

Indicate Slave ID#2 data interchange
status on PLC LINK

M1378*

Indicate Slave ID#3 data interchange
status on PLC LINK

M1379*

Indicate Slave ID#4 data interchange
status on PLC LINK

M1380*

Indicate Slave ID#5 data interchange
status on PLC LINK

M1381*

Indicate Slave ID#6 data interchange
status on PLC LINK

M1382*

Indicate Slave ID#7 data interchange
status on PLC LINK

M1383*

Indicate Slave ID#8 data interchange
status on PLC LINK

M1384*

Indicate Slave ID#9 data interchange
status on PLC LINK

M1385*

Indicate Slave ID#10 data interchange
status on PLC LINK

M1386*

Indicate Slave ID#11 data interchange
status on PLC LINK

M1387*

Indicate Slave ID#12 data interchange
status on PLC LINK

M1388*

Indicate Slave ID#13 data interchange
status on PLC LINK

M1389*

Indicate Slave ID#14 data interchange
status on PLC LINK

M1390*

Indicate Slave ID#15 data interchange
status on PLC LINK

M1391*

Indicate Slave ID#16 data interchange
status on PLC LINK

M1392*

Slave ID#1 linking error

M1393*

Slave ID#2 linking error

M1394*

Slave ID#3 linking error

M1395*

Slave ID#4 linking error

M1396*

Slave ID#5 linking error

M1397*

Slave ID#6 linking error

M1398*

Slave ID#7 linking error

M1399*

Slave ID#8 linking error

M1400*

Slave ID#9 linking error

M1357*

Enabling the detection of X0’s input pulse
frequency (ON: Enable; OFF: Disable)

M1358*

Enablling the detection of X1’s input pulse
frequency (ON: Enable; OFF: Disable)

M1359*

Enablling the detection of X2’s input pulse
frequency (ON: Enable; OFF: Disable)

M1360*

Slave ID#1 status on PLC LINK network

M1361*

Slave ID#2 status on PLC LINK network

M1362*

Slave ID#3 status on PLC LINK network

M1363*

Slave ID#4 status on PLC LINK network

M1364*

Slave ID#5 status on PLC LINK network

M1365*

Slave ID#6 status on PLC LINK network

M1366*

Slave ID#7 status on PLC LINK network

M1367*

Slave ID#8 status on PLC LINK network

M1368*

Slave ID#9 status on PLC LINK network

M1369*

Slave ID#10 status on PLC LINK network

M1370*

Slave ID#11 status on PLC LINK network

M1371*

Slave ID#12 status on PLC LINK network

M1372*

Slave ID#13 status on PLC LINK network

M1373*

Slave ID#14 status on PLC LINK network

M1374*

Slave ID#15 status on PLC LINK network

M1375*

Slave ID#16 status on PLC LINK network

M1376*

Indicate Slave ID#1 data interchange
status on PLC LINK

M1377*

Indicate Slave ID#2 data interchange
status on PLC LINK

M1378*

Indicate Slave ID#3 data interchange
status on PLC LINK

M1379*

Indicate Slave ID#4 data interchange
status on PLC LINK

M1380*

Indicate Slave ID#5 data interchange
status on PLC LINK

M1381*

Indicate Slave ID#6 data interchange
status on PLC LINK

M1382*

Indicate Slave ID#7 data interchange
status on PLC LINK

M1383*

Indicate Slave ID#8 data interchange
status on PLC LINK

M1384*

Indicate Slave ID#9 data interchange
status on PLC LINK

M1385*

Indicate Slave ID#10 data interchange
status on PLC LINK

M1386*

Indicate Slave ID#11 data interchange
status on PLC LINK

M1387*

Indicate Slave ID#12 data interchange
status on PLC LINK

M1388*

Indicate Slave ID#13 data interchange
status on PLC LINK

M1389*

Indicate Slave ID#14 data interchange
status on PLC LINK

M1390*

Indicate Slave ID#15 data interchange
status on PLC LINK

M1391*

Indicate Slave ID#16 data interchange
status on PLC LINK

M1392*

Slave ID#1 linking error

M1393*

Slave ID#2 linking error

M1394*

Slave ID#3 linking error

M1395*

Slave ID#4 linking error

M1396*

Slave ID#5 linking error

M1397*

Slave ID#6 linking error

M1398*

Slave ID#7 linking error

M1399*

Slave ID#8 linking error

M1400*

Slave ID#9 linking error

M1437*

Indicate that writing to Slave ID#14 is
completed

M1438*

Indicate that writing to Slave ID#15 is
completed

M1439*

Indicate that writing to Slave ID#16 is
completed

M1524

Auto-reset Y2 when high speed pulse
output is completed

M1525

Auto-reset Y3 when high speed pulse
output is completed

M1534

Enable ramp-down time setting on Y0.
Has to be used with D1348.

M1535

Enable ramp-down time setting on Y2.
Has to be used with D1349.

M1538

Indicate pause status of Y0

M1539

Indicate pause status of Y1

M1540

Indicate pause status of Y2

M1541

Indicate pause status of Y3

M1580

The absolute position of Delta ASDA-A2
servo is read successfully by means of
the instruction DABSR.

M1581

The absolute position of Delta ASDA-A2
servo is not read successfully by means
of the instruction DABSR.

M1584

If the left limit switch of CH0 is enabled, it
can be triggered either by a rising-edge
signal or by a falling-edge signal. (OFF:
Rising-edge signal; ON: Falling-edge
signal)

M1585

If the left limit switch of CH1 is enabled, it
can be triggered either by a rising-edge
signal or by a falling-edge signal. (OFF:
Rising-edge signal; ON: Falling-edge
signal)

M1590

Enabling the acceleration of the Ethernet
data exchange (ON: Enable; OFF:
Disable)

M1598*

Enabling the fetching of the value in the
hardware counter
C243/C245/C246/C247/C248/C251/C252
, and using X6 as a fetching signal (ON:
Enable; OFF: Disable)

M1599*

Enabling the fetching of the value in the
hardware counter
C244/C249/C250/C253/C254, and using
X7 as a fetching signal (ON: Enable;
OFF: Disable)

M1700~
1731

Enabling to read the code 0X04 of the
Slave ID1 from PLC Link (available for
ES2, EX2, ES2-C, ES2-E V3.48/12SA2
V3.0/SX2 V3.0/26SE V2.0/28SA2 V3.0 or
later versions)

Special register device on PLC DELTA

D1000*

Setting value of the watchdog timer (WDT)
(Unit: 1ms)

D1001

Displaying the firmware version of DVP
PLC (For example, the firmware version is
1.0 if the value in D1001 is HXX10.)

D1002*

Program capacity (ES2/EX2/SA2/SX2:
15872; SS2: 7920)

D1003

Sum of the PLC internal program memory
(ES2/EX2/SA2/SX2: -15872; SS2: -7920)

D1004*

Syntax check error code

D1008*

Step address when WDT is ON

D1009

Number of LV (Low voltage) signal
occurrence

D1010*

Current scan time (Unit: 0.1ms)

D1011*

Minimum scan time (Unit: 0.1ms)

D1012*

Maximum scan time (Unit: 0.1ms)

D1015*

Value of accumulative high-speed timer
(0~32,767, unit: 0.1ms)

D1018*

π PI (Low byte)

D1019*

π PI(High byte)

D1020*

X0~X7 input filter (unit: ms) 0~20ms
adjustable

D1021*

X10~X17 X7 input filter (unit: ms) 0~20ms
adjustable (available for ES2-E V3.48/SS2
V3.42/SA2 V3.0/SE V2.0 or later versions)

D1022

Counting mode selection (Double
frequency/ 4 times frequency) for AB phase
counter (From X0, X1 input)

D1023*

Register for Storing detected pulse width
(unit: 0.1ms)

D1025*

Code for communication request error

D1026*

The pulse number for masking Y0 is set
when M1156 = ON (Low word)

D1027*

The pulse number for masking Y0 is set
when M1156 = ON (High word)
If the value in the 32-bit register (D1027,
D1026) is less than or equal to 0, the
function will not be enabled. (Default value:
0)

D1028

Index register E0

D1029

Index register F0

D1030

PV of Y0 pulse output (Low word)

D1031

PV of Y0 pulse output (High word)

D1032

PV of Y1 pulse output (Low word)

D1033

PV of Y1 pulse output (High word)

D1036*

COM1 (RS-232) communication protocol

D1037*

Register for setting 8-sets SPD function
(has to be used with M1037)

D1038

1. Delay time setting for data response
when PLC is SLAVE in COM2 / COM3 RS-
485 communication. Range: 0 ~ 10,000
(unit: 0.1ms).
2. By using PLC LINK in COM2 (RS-485),
D1038 can be set to send next
communication data with delay. Range: 0 ~
10,000 (Unit: one scan cycle)

D1039*

Fixed scan time (ms)

D1040

No. of the 1st step point which is ON.

D1041

No. of the 2nd step point which is ON

D1042

No. of the 3rd step point which is ON.

D1043

No. of the 4th step point which is ON

D1044

No. of the 5th step point which is ON.

D1045

No. of the 6th step point which is ON

D1046

No. of the 7th step point which is ON.

D1047

No. of the 8th step point which is ON

D1049

No. of alarm which is ON

D1050

D1055

Processing MODRD communication data
The PLC automatically converts the data in
D1070~D1085 in the ASCII mode into
hexadecimal values, or combines two lower
8 bits in the RTU mode into 16 bits in the
RTU mode.

D1056*

Low word of X0’s input pulse frequency
(Unit: 0.001Hz)
It is used with M1357.

D1057*

High word of X0’s input pulse frequency
(Unit: 0.001Hz)
It is used with M1357.

D1058*

Low word of X1’s input pulse frequency
(Unit: 0.001Hz)
It is used with M1358.

D1059*

High word of X1’s input pulse frequency
(Unit: 0.001Hz)
It is used with M1358.

D1062*

Average number of times an analog signal
is input to the EX2/SX2 series PLC
The default value is K10 for EX2 version
2.6 and version 2.8.

D1067*

Error code for program execution error

D1068*

Address of program execution error

D1070

D1085

Feedback data (ASCII) of Modbus
communication. When PLC’s RS-485
communication instruction receives
feedback signals, the data will be saved in
the registers D1070~D1085. Usres can
check the received data in these registers.

D1086

High word of the password in DVP-PCC01
(displayed in hex according to its ASCII
codes)

D1087

Low word of the password in DVP-PCC01
(displayed in hex according to its ASCII
codes)

D1089

D1099

Sent data of Modbus communication.
When PLC’s RS-485 communication
instruction sends out data, the data will be
stored in D1089~D1099. Users can check
the sent data in these registers.

D1109*

COM3 (RS-485) Communication protocol

D1110*

Average value of EX2/SX2 analog input
channel 0 (AD 0) When average times in
D1062 is set to 1, D1110 indicates present
value.

D1111*

Average value of EX2/SX2 analog input
channel 1 (AD 1) When average times in
D1062 is set to 1, D1111 indicates present
value

D1112*

Average value of EX2/SX2 analog input
channel 2 (AD 2) Whenaverage times in
D1062 is set to 1, D1112 indicates present
value

D1113*

Average value of 20EX2/SX2 analog input
channel 3 (AD 3) Whenaverage times in
D1062 is set to 1, D1113 indicates present
value

Displaying the status of the analog input
channel of 30EX2

D1114*

Enable/disable 20EX2/SX2 AD channels
(0: enable (default) / 1: disable)
bit0~bit3 sets AD0~AD3.
P.S. 30EX2 does not support this function.

D1115*

20EX2/SX2 analog input/output mode
setting

30EX2 analog input/output mode setting

D1116*

Output value of analog output channel 0
(DA 0) of EX2/SX2

D1117*

Output value of analog output channel 1
(DA 0) of 20EX2/SX2
P.S. 30EX2 does not support this function.

D1118*

EX2/SX2 sampling time of analog/digital
converstion. Default: 2. Unit: 1ms.
Sampling time will be regarded as 2ms if
D1118
2

D1120*

COM2 (RS-485) communication protocol

D1121*

COM1(RS-232) and COM2(RS-485) PLC
communication address

D1122

COM2(RS-485) Residual number of words
of transmitting data

D1123

COM2(RS-485) Residual number of words
of the receiving data

D1124

COM2(RS-485) Definition of start character
(STX)

D1125

COM2(RS-485) Definition of first ending
character (ETX1)

D1126

COM2(RS-485) Definition of second ending
character (ETX2)

D1127

Number of pulses for ramp-up operation of
positioning instruction (Low word)

D1128

Number of pulses for ramp-up operation of
positioning instruction (High word)

D1129

COM2 (RS-485) Communication time-out
setting (ms)

D1130

COM2 (RS-485) Error code returning from
Modbus

D1131

Input/output percentage value of
CH0(Y0,Y1) close loop control

D1132

Input/output percentage value of
CH1(Y2,Y3) close loop control

D1133

Number of pulses for ramp-down operation
of positioning instruction (Low word)

D1134

Number of pulses for ramp-down operation
of positioning instruction (High word)

D1135*

Pulse number for masking Y2 when M1158
= ON (Low word)

D1136*

Pulse number for masking Y2 when M1158
= ON (High word)

D1137*

Address where incorrect use of operand
occurs

D1140*

Number of I/O modules (max. 8)

D1142*

Number of input points (X) on DIO modules

D1143*

Number of output points (Y) on DIO
modules

D1145*

Number of the connected let-side modules

D1150*

Vale fetched from the hardware counter
C243/C245/C246/C247/C248/C251/C252
(Low word)

D1151*

Value fetched from the hardware counter
C243/C245/C246/C247/C248/C251/C252
(High word)

D1152*

Value fetched from the hardware counter
C244/C249/C250/C253/C254 (Low word)

D1153*

Value fetched from the hardware conter
C244/C249/C250/C253/C254 (High word)

D1167

The specific end word to be detected for
RS instruction to execute an interruption
request (I140) on COM1 (RS-232).

D1168

The specific end word to be detected for
RS instruction to execute an interruption
request (I150) on COM2 (RS-485)

D1169

The specific end word to be detected for
RS instruction to execute an interruption
request (I160) on COM3 (RS-485)

D1178

VR0 value

D1179

VR1 value

D1182

Index register E1

D1183

Index register F1

D1184

Index register E2

D1185

Index register F2

D1186

Index register E3

D1187

Index register F3

D1188

Index register E4

D1189

Index register F4

D1190

Index register E5

D1191

Index register F5

D1192

Index register E6

D1193

Index register F6

D1194

Index register E7

D1195

Index register F7

D1220

Pulse output mode setting of CH0 (Y0, Y1)

D1221

Pulse output mode setting of CH1 (Y2, Y3)

D1232*

Number of output pulses for CH0 (Y0, Y1)
ramp-down stop when mark sensor
receives signals. (Low word).

D1233*

Number of output pulses for CH0 (Y0, Y1)
ramp-down stop when mark sensor
receives signals. (High word).

D1234*

Number of output pulses for CH1 (Y2, Y3)
ramp-down stop when mark sensor
receives signals. (Low word).

D1235*

Number of output pulses for CH2 (Y2, Y3)
ramp-down stop when mark sensor
receives signals. (High word).

D1240*

When interupt I400/I401/I100/I101 occurs,
D1240 stores the low word of high-speed
counter.

D1241*

When interupt I400/I401/I100/I101 occurs,
D1241 stores the high Word of high-speed
counter.

D1242*

When interupt I500/I501/I300/I301 occurs,
D1242 stores the low Wordof high-speed
counter.

D1243*

When interupt I500/I501/I300/I301 occurs,
D1243 stores the high Word of high-speed
counter.

D1244

Idle time (pulse number) setting of CH0 (Y0,
Y1) The function is disabled if set value
0.

D1245

Idle time (pulse number) setting of CH1 (Y2,
Y3) The function is disabled if set value
0.

D1246*

Low word of X2’s input pulse frequency
(Unit: 0.01Hz)
It is used with M1359.

D1247*

High word of X2’s input pulse frequency
(Unit: 0.01Hz)
It is used with M1359.

D1249

Set value for COM1 (RS-232) data
receiving time-out (Unit: 1ms, min. 50ms,
value smaller than 50ms will be regarded
as 50ms) (only applicable for MODRW/RS
instruction) In RS instruction, no time-out
setting if “0” is specified.

D1250

COM1 (RS-232) communication error code
(only applicable for MODRW/RS
instruction)

D1252

Set value for COM3 (RS-485) data
receiving time-out (Unit: 1ms, min. 50ms,
value smaller than 50ms will be regarded
as 50ms) (only applicable for MODRW/RS
instruction) In RS instruction, no time-out
setting if “0” is specified

D1253

COM3 (RS-485) communication error code
(only applicable for MODRW/RS
instruction)

D1255*

COM3 (RS-485) PLC communication
address

D1256

D1295

For COM2 RS-485 MODRW instruction.
D1256~D1295 store the sent data of
MODRW instruction. When MODRW
instruction sends out data, the data will be
stored in D1256~D1295. Users can check
the sent data in these registers.

D1296

D1311

For COM2 RS-485 MODRW instruction.
D1296~D1311 store the converted hex data
from D1070 ~ D1085 (ASCII). PLC
automatically converts the received ASCII
data in D1070 ~ D1085 into hex data.

D1312*

Specify the number of additional pulses for
additional pulses output and Z-phase
seeking function of ZRN instruction (Has to
be used with M1308)

D1313*

Second of RTC: 00 ~ 59

D1314*

Minute of RTC: 00 ~ 59

D1315*

Hour of RTC: 00 ~ 23

D1316*

Day of RTC: 01 ~ 31

D1317*

Month of RTC: 01 ~ 12

D1318*

Week of RTC: 1 ~ 7

D1319*

Year of RTC: 00 ~ 99 (A.D.)

D1320*

ID of the 1st right side module

D1321*

ID of the 2nd right side module

D1322*

ID of the 3rd right side module

D1323*

ID of the 4th right side module

D1324*

ID of the 5th right side module

D1325*

ID of the 6th right side module

D1326*

ID of the 7th right side module

D1327*

ID of the 8th right side module

D1336

PV of Y2 pulse output (Low word)

D1337

PV of Y2 pulse output (High word)

D1338

PV of Y3 pulse output (Low word)

D1339

PV of Y3 pulse output (High word)

D1340

Start/end frequency of the 1st group pulse
output CH0 (Y0, Y1)

D1343

Ramp up/down time of the 1st group pulse
output CH0 (Y0, Y1)

D1348*

When M1534 = ON, D1348 stores the
ramp-down time of CH0(Y0, Y1) pulse
output.

D1349*

When M1535 = ON, D1349 stores the
ramp-down time of CH1(Y2, Y3) pulse
output.

D1352

Start/end frequency of the 2nd group pulse
output CH1 (Y2, Y3)

D1353

Ramp up/down time of the 2nd group pulse
output CH1 (Y2, Y3)

D1354

PLC Link scan cycle (Unit: 1ms)
n Max: K32000
n D1354 = K0 when PLC Link stops or
when the first scan is completed

D1355*

Starting reference for Master to read from
Slave ID#1

D1356*

Starting reference for Master to read from
Slave ID#2

D1357*

Starting reference for Master to read from
Slave ID#3

D1358*

Starting reference for Master to read from
Slave ID#4

D1359*

Starting reference for Master to read from
Slave ID#5

D1360*

Starting reference for Master to read from
Slave ID#6

D1361*

Starting reference for Master to read from
Slave ID#7

D1362*

Starting reference for Master to read from
Slave ID#8

D1363*

Starting reference for Master to read from
Slave ID#9

D1364*

Starting reference for Master to read from
Slave ID#10

D1365*

Starting reference for Master to read from
Slave ID#11

D1366*

Starting reference for Master to read from
Slave ID#12

D1367*

Starting reference for Master to read from
Slave ID#13

D1368*

Starting reference for Master to read from
Slave ID#14

D1369*

Starting reference for Master to read from
Slave ID#15

D1370*

Starting reference for Master to read from
Slave ID#16

D1386

ID of the 1st left side module

D1387

ID of the 2nd left side module

D1388

ID of the 3rd left side module

D1389

ID of the 4th left side module

D1390

ID of the 5th left side module

D1391

ID of the 6th left side module

D1392

ID of the 7th left side module

D1393

ID of the 8th rleft side module

D1399*

Starting ID of Slave designated by PLC
LINK

D1415*

Starting reference for Master to write in
Slave ID#1

D1416*

Starting reference for Master to write in
Slave ID#2

D1417*

Starting reference for Master to write in
Slave ID#3

D1418*

Starting reference for Master to write in
Slave ID#4

D1419*

Starting reference for Master to write in
Slave ID#5

D1420*

Starting reference for Master to write in
Slave ID#6

D1421*

Starting reference for Master to write in
Slave ID#7

D1422*

Starting reference for Master to write in
Slave ID#8

D1423*

Starting reference for Master to write in
Slave ID#9

D1424*

Starting reference for Master to write in
Slave ID#10

D1425*

Starting reference for Master to write in
Slave ID#11

D1426*

Starting reference for Master to write in
Slave ID#12

D1427*

Starting reference for Master to write in
Slave ID#13

D1428*

Starting reference for Master to write in
Slave ID#14

D1429*

Starting reference for Master to write in
Slave ID#15

D1430*

Starting reference for Master to write in
Slave ID#16

D1431*

Times of PLC LINK polling cycle

D1432*

Current times of PLC LINK polling cycle

D1433*

Number of slave units linked to EASY PLC
LINK

D1434*

Data length to be read on Slave ID#1

D1435*

Data length to be read on Slave ID#2

D1436*

Data length to be read on Slave ID#3

D1437*

Data length to be read on Slave ID#4

D1438*

Data length to be read on Slave ID#5

D1439*

Data length to be read on Slave ID#6

D1440*

Data length to be read on Slave ID#7

D1441*

Data length to be read on Slave ID#8

D1442*

Data length to be read on Slave ID#9

D1443*

Data length to be read on Slave ID#10

D1444*

Data length to be read on Slave ID#11

D1445*

Data length to be read on Slave ID#12

D1446*

Data length to be read on Slave ID#13

D1447*

Data length to be read on Slave ID#14

D1448*

Data length to be read on Slave ID#15

D1449*

Data length to be read on Slave ID#16

D1450*

Data length to be written on Slave ID#1

D1451*

Data length to be written on Slave ID#2

D1452*

Data length to be written on Slave ID#3

D1453*

Data length to be written on Slave ID#4

D1454*

Data length to be written on Slave ID#5

D1455*

Data length to be written on Slave ID#6

D1456*

Data length to be written on Slave ID#7

D1457*

Data length to be written on Slave ID#8

D1458*

Data length to be written on Slave ID#9

D1459*

Data length to be written on Slave ID#10

D1460*

Data length to be written on Slave ID#11

D1461*

Data length to be written on Slave ID#12

D1462*

Data length to be written on Slave ID#13

D1463*

Data length to be written on Slave ID#14

D1464*

Data length to be written on Slave ID#15

D1465*

Data length to be written on Slave ID#16

D1480*

D1495*

The data which is read from slave ID#1 in
the PLC LINK at the time when M1353 is
OFF

The initial data register where the data read
from slave ID#1~ID#16 in the PLC LINK is
stored at the time when M1353 is ON

D1496*

D1511*

The data which is written into slave ID#1 in
the PLC LINK at the time when M1353 is
OFF

The initial data register where the data
written into slave ID#1~ID#16 in the PLC
LINK is stored at the time when M1353 is
ON

D1512*

D1527*

The data which is read from slave ID#2 in
the PLC LINK

D1528*

D1543*

The data which is written into slave ID#2 in
the PLC LINK

D1544*

D1559*

The data which is read from slave ID#3 in
the PLC LINK

D1560*

D1575*

The data which is written into slave ID#3 in
the PLC LINK

D1576*

D1591*

The data which is read from slave ID#4 in
the PLC LINK

D1592*

D1607*

The data which is written into slave ID#4 in
the PLC LINK

D1608*

D1623*

The data which is read from slave ID#5 in
the PLC LINK

D1624*

D1639*

The data which is written into slave ID#5 in
the PLC LINK

D1640*

D1655*

The data which is read from slave ID#6 in
the PLC LINK

D1656*

D1671*

The data which is written into slave ID#6 in
the PLC LINK

D1672*

D1687*

The data which is read from slave ID#7 in
the PLC LINK

D1688*

D1703*

The data which is written into slave ID#7 in
the PLC LINK

D1704*

D1719*

The data which is read from slave ID#8 in
the PLC LINK

D1720*

D1735*

The data which is written into slave ID#8 in
the PLC LINK

D1736*

D1751*

The data which is read from slave ID#9 in
the PLC LINK

D1752*

D1767*

The data which is written into slave ID#9 in
the PLC LINK

D1768*

D1783*

The data which is read from slave ID#10 in
the PLC LINK

D1784*

D1799*

The data which is written into slave ID#10
in the PLC LINK

D1800*

D1815*

The data which is read from slave ID#11 in
the PLC LINK

D1816*

D1831*

The data which is written into slave ID#11
in the PLC LINK

D1832*

D1847*

The data which is read from slave ID#12 in
the PLC LINK

D1848*

D1863*

The data which is written into slave ID#12
in the PLC LINK

D1864*

D1879*

The data which is read from slave ID#13 in
the PLC LINK

D1880*

D1895*

The data which is written into slave ID#13
in the PLC LINK

D1896*

D1911*

The data which is read from slave ID#14 in
the PLC LINK

D1900*

D1931*

Specify the station number of Slaves for
PLC-Link when M1356 is ON. Consecutive
station numbers set by D1399 will be
invalid in this case. Note that the registers
are latched only when M1356 is ON.

D1912*

D1927*

The data which is written into slave ID#14
in the PLC LINK

D1928*

D1943*

The data which is read from slave ID#15 in
the PLC LINK

D1944*

D1959*

The data which is written into slave ID#15
in the PLC LINK

D1960*

D1975*

The data which is read from slave ID#16 in
the PLC LINK

D1976*

D1991*

The data which is written into slave ID#16
in the PLC LINK

D1994

Remaining times for PLC password setting
on DVP-PCC01

D1995

Data length for PLC ID Setting on DVP
PCC01

D1996

1st Word of PLC ID Setting for DVP-PCC01
(Indicated by Hex format corresponding to
ASCII codes)

D1997

2nd Word of PLC ID Setting for DVP-PCC01
(Indicated by Hex format corresponding to
ASCII codes)

D1998

3rd Word of PLC ID Setting for DVP-PCC01
(Indicated by Hex format corresponding to
ASCII codes)

D1999

4th word of PLC ID Setting for DVP-PCC01
(Indicated by Hex format corresponding to
ASCII codes)

D9800~
D9879

They are for left-side special modules
which are connected to an SA2/SX2/SE
series MPU.

D9900~
D9979

They are for special modules connected to
an ES2/EX2 series MPU. (Please refer to
DVP-PLC Operation Manual – Modules
for more information)
They are for right-side special modules
connected to an SA2/SX2/SE series MPU.

D9980

CANopen status message code
(Only for DVP-ES2-C series MPUs)

D9981~
D9996

(Only for DVP-ES2-C series MPUs)
CANopen status message code in slave
station 1~slave station 16

D9998

Bit0~15 represent station 1~station 16. If a
bit is ON, an error occurs.
(It is only applicable to DVP-ES2-C series
MPUs. If DVP-ES2-C V3.24 (or above) is
turned from OFF to ON, the value in D9998
will be H’0. If DVP-ES2-C V3.26 (or above)
is turned from OFF to ON, the value in
D9998 will be H’FFFF.)

D9999

Showing the CAN baud rate
K1: 20K; K2: 50K; K3: 125K; K4: 250K; K5:
500K; K6: 1M
(It is only applicable to DVP-ES2-C V3.26
and above.)